Four Style B (Class B) Initiating Device Circuits (IDCs).
-
One Master Panel also has two zones, each zone can connect max.25 conventional detectors.
-
One slave Panel has two zones, each zone can connect max.25 conventional detectors.
-
The Mater panel could show the fire and fault of all slave panel. The slave panel can only show itself fire and fault.
-
Mini size as 108X143X40mm
-
Master panel has 4 digital LED display to show slave number and status.
-
2 Detection Zones Panel, 25 Detectors per Zone
-
Fire 1 relay would be activated when one zone alarms.
-
Fire 2 relay would be activated after 30 seconds delay when two zones alarm.
-
1 Sound relay output for sound alarm
-
1 Fault relay output for fault condition
-
Zones Fire and Fault LEDs indication
-
Fire1, Fire2, Sound relay outputs can be activated manually
-
RS485 Port for repeater up to 1.2Km
-
Up to 31 Slave panels can be connected to one Master panel
-
Powered by outside DC22-26V power supply
-
End Of Line Status Detection, Short circuit /open circuit detection
-
Two modules power supply could be selected.
-
The power supply input is AC90-270V
-
Two 4AH batteries can be housed in the power supply cabinet.
-
Relay output contacts rated at: 2.0 amps @ 30 VDC.
|